Technical data
Series
Quad
Type
RMZ-1215-R40
Applications
Measuring range
NTC : -40°C to +60°C PT100 : -190°C to +260°C (depending on sensor type)
Accuracy
NTC : ±0,5°C (-20°C up to 60°C) with calibration PT100 : ± 0,3°C (-20°C up to +60°C) with calibration
Resolution
0.1°C
WAN interface
SIM Card
Number of nodes supported
Zigbee repeater function supports 20 nodes. Unlimited number of repeaters form mesh network.
Memory
10.082 samples
Buffer memory
Storage temperature
-40°C to +55°C
Sensors
2x wired external PT100, 1x wired external NTC or potential free contact input (non triggered)
Measuring rate
Standard 15 min, can be set 1 min to 24 h
Measuring mode
Power
+12Vdc EU external adapter (included) (+24Vdc and International power plug versions available)
Battery life
Protection class
IP 40
Housing
Polycarbonate, UV stabilized
Dimensions
92 X 141 X 62mm
Weight
200 g
Certifications
CE
Radio frequency
2.400-2.483,5 GHz (Zigbee)
Transmit power
6.3mW (Zigbee)
Transmission distance
Up to 60m indoor, 1000m outdoor (Zigbee)
Energy consumption
80mA
Wireless
Zigbee
Antenna
External whip antenna (Zigbee)